Mauricio Torres, Pere Alavedra, Amado Guzmán, Eva Cuerva, Carla Planas, Raquel Clemente, Vanessa Escalona
building simulation
double skin façade
energy efficiency
Cooling loads
energy saving.
Languages
English
Bibliographic info
Building Simulation, 2007, Beijing, China

Taking into account Mediterranean climate particularities for Barcelona, Spain, a whole year study using TAS simulation software was carried out for a Double Skin Façade corporative office building. It is a typical office building with an extended working hours schedule for acclimatization. Four different cavity widths were simulated – 40cm, 60cm, 80cm, 100cm - as well as three different external opening areas for cavity’s natural ventilation purpose. Two Double Skin Façade typologies were simulated – a corridor façade and a multistory façade. Simulations showed cooling loads are much greater than heating loads on a double glazed skin façade building south oriented in a Mediterranean climate town like Barcelona. Results demonstrated that a Multistory Façade, depending on its configuration, might save up to 5% on annual cooling loads respect to a Corridor Façade. Different opening areas and cavity depths shall be used for different typologies in order to obtaining good energy results.