Skip to main content
Publi image
Publi data
Adam Martin Rysanek, Murray Portia Jayne, Jovan Pantelic, Matthias Mast, Arno Schlueter
Languages
English
Bibliographic info
Building Simulation, 2015, Hyderabad, India

This paper presents a simulation-based study of a decentralized, „low-exergy‟ (or LowEx) space cooling system for a commercial office currently under construction in Singapore. We used asdesigned building and system characteristics to parametrize a TRNSYS simulation model of the energy supply system. We also compared the performance of the LowEx air-conditioning system against a conventional air handling unit. Our study indicates that the LowEx concept can reduce electricity consumption for space cooling by up to 40% when complemented by a low-lift chiller and as high as 20% when driven by standard chillers.